Aerco ProtoNode Gateway Rev 1 (with internal LEDs) Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 64
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
Page 17 of 64
USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288 VD2:011712
1
GF-129
5. INSTALL AND RUN THE UTILITY SOFTWARE TO SETUP IP ADDRESS FOR BACNET/IP
Download the RUINET Utilities from the ProtoCessor web site (under Tech Support Utilities
Utilities SoftwareInstall.zip) or access the page at:
http://www.protocessor.com/tech_support/Design_Documents.html#US
Run Install.zip and follow the installation instructions
Once installed, the FieldServer Utilities can be located in the Windows Start menu as a desktop icon
5.1 Connect the PC to the ProtoNode via the Ethernet port
Figure 11. Ethernet port location of ProtoNode
Disable any wireless Ethernet adapters on the PC/Laptop
Disable firewall and virus protection software
Connect a standard cat5 Ethernet cable between the PC and ProtoNode.
The Default IP Address of the ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and
the ProtoNode are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx
network.
Go to > >
Right-click on Local Area Connection > Properties
Highlight >
Select: Use the following IP address
Click twice
Go to Start > Programs > Field Server Utilities > Ruiping Utility
Vista de pagina 16