Page 37 of 64
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
GF-129
Equipment Point Name Name
Read
BACnet Type:ID N2 Type N2 ID Lon SNVT NAME Lon SNVT Lon Direction
ModBus/Unit
10-Run Hours runhours_2
AV:45 data float 20 nvoRunHours2 51 Output (non-polled)
Blr Addr 3
01-Fire Rate Out boilerstate_3
AV:54 data float 21 nvoBlrState3 inc count (9) Output (non-polled)
02-Active Setpoint effectsetpt_3
AV:55 data float 22 nvoEffSetpt3 inc count (9) Output (non-polled)
30017/3
03-Net Remote Setpt setpt_3 AV:56 data float 23 nviSetpt3 inc count (9) Input (non-polling)
05-Fire Rate In boilerload_3
AV:60 data float 25 nvoBlrLoad3 inc count (9) Output (non-polled)
30018/3
06-Outlet Temp localsuptemp_3
AV:61 data float 26 nvoLocSupTmp3 inc count (9) Output (non-polled)
07-Display Code dispcode_3
AV:62 data float 27 nvoDispCode3 inc count (9) Output (non-polled)
30001/3
08-Unit Status unitstat_3
AV:63 data float 28 nvoUnitStat3 inc count (9) Output (non-polled)
09-Run Cycles runcycles_3
AV:58 data float 29 nvoRunCycles3 51 Output (non-polled)
30012-30013/3
10-Run Hours runhours_3
AV:59 data float 30 nvoRunHours3 51 Output (non-polled)
Blr Addr 4
01-Fire Rate Out boilerstate_4
AV:70 data float 31 nvoBlrState4 inc count (9) Output (non-polled)
02-Active Setpoint effectsetpt_4
AV:71 data float 32 nvoEffSetpt4 inc count (9) Output (non-polled)
30017/4
03-Net Remote Setpt setpt_4 AV:72 data float 33 nviSetpt4 inc count (9) Input (non-polling)
05-Fire Rate In boilerload_4
AV:73 data float 35 nvoBlrLoad4 inc count (9) Output (non-polled)
30018/4
06-Outlet Temp localsuptemp_4
AV:65 data float 36 nvoLocSupTmp4 inc count (9) Output (non-polled)
07-Display Code dispcode_4
AV:66 data float 37 nvoDispCode4 inc count (9) Output (non-polled)
30001/4
08-Unit Status unitstat_4
AV:67 data float 38 nvoUnitStat4 inc count (9) Output (non-polled)
09-Run Cycles runcycles_4
AV:68 data float 39 nvoRunCycles4 51 Output (non-polled)
30012-30013/4
10-Run Hours runhours_4
AV:69 data float 40 nvoRunHours4 51 Output (non-polled)
Blr Addr 5
01-Fire Rate Out boilerstate_5
AV:80 data float 41 nvoBlrState5 inc count (9) Output (non-polled)
02-Active Setpoint effectsetpt_5
AV:81 data float 42 nvoEffSetpt5 inc count (9) Output (non-polled)
30017/5
03-Net Remote Setpt setpt_5 AV:82 data float 43 nviSetpt5 inc count (9) Input (non-polling)
05-Fire Rate In boilerload_5
AV:74 data float 45 nvoBlrLoad5 inc count (9) Output (non-polled)
30018/5
06-Outlet Temp localsuptemp_5
AV:75 data float 46 nvoLocSupTmp5 inc count (9) Output (non-polled)
07-Display Code dispcode_5
AV:76 data float 47 nvoDispCode5 inc count (9) Output (non-polled)
30001/5
08-Unit Status unitstat_5
AV:77 data float 48 nvoUnitStat5 inc count (9) Output (non-polled)
09-Run Cycles runcycles_5
AV:78 data float 49 nvoRunCycles5 51 Output (non-polled)
30012-30013/5
10-Run Hours runhours_5
AV:79 data float 50 nvoRunHours5 51 Output (non-polled)
Blr Addr 6
01-Fire Rate Out boilerstate_6
AV:90 data float 51 nvoBlrState6 inc count (9) Output (non-polled)
C.2.2 - Eight C-Mores and One ACS/BMS II/BMS (Cont.)