AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
GF-129
Equipment Point Name Name
Read
BACnet Type:ID N2 Type N2 ID Lon SNVT NAME Lon SNVT Lon Direction
ModBus/Unit
04-Header Temp
localsuptemp_1
3
AV:34 data float 124 nvoLocSupTmp inc count (9) Output (non-polled)
05-Outside Air Temp localoatemp_13
AV:35 data float 125 nvoLocOATmp inc count (9) Output (non-polled)
30003/128
06-Display Code dispcode_13
AV:36 data float 126 nvoDispCode inc count (9) Output (non-polled)
07-Num Boilers Fired blrfired_13
AV:37 data float 127 nvoBlrsFired inc count (9) Output (non-polled)
30008/128
08-Num Boilers
Online
blronline_13
AV:38 data float 128 nvoBlrsOnline inc count (9) Output (non-polled)
30009/128
09-Last Blr Fired blrlast_13
AV:39 data float 129 nvoLastBlrFired inc count (9) Output (non-polled)
10-Boiler 1 Status blr1stat_13
AV:40 data float 130 nvoBlr1Stat inc count (9) Output (non-polled)
30018/128
11-Boiler 2 Status blr2stat_13
AV:41 data float 131 nvoBlr2Stat inc count (9) Output (non-polled)
12-Boiler 3 Status blr3stat_13
AV:48 data float 132 nvoBlr3Stat inc count (9) Output (non-polled)
30020/128
13-Boiler 4 Status blr4stat_13
AV:1 data float 133 nvoBlr4Stat inc count (9) Output (non-polled)
14-Boiler 5 Status blr5stat_13
AV:2 data float 134 nvoBlr5Stat inc count (9) Output (non-polled)
30022/128
15-Boiler 6 Status blr6stat_13
AV:3 data float 135 nvoBlr6Stat inc count (9) Output (non-polled)
16-Boiler 7 Status blr7stat_13
AV:4 data float 136 nvoBlr7Stat inc count (9) Output (non-polled)
30024/128
17-Boiler 8 Status blr8stat_13
AV:5 data float 137 nvoBlr8Stat inc count (9) Output (non-polled)
18-Net Blr 1 Status blr9stat_13
AV:6 data float 138 nvoNetBlr1Stat inc count (9) Output (non-polled)
30026/128
19-Net Blr 2 Status blr10stat_13
AV:7 data float 139 nvoNetBlr2Stat inc count (9) Output (non-polled)
20-Net Blr 3 Status blr11stat_13
AV:8 data float 140 nvoNetBlr3Stat inc count (9) Output (non-polled)
30028/128
21-Net Blr 4 Status blr12stat_13
AV:9 data float 141 nvoNetBlr4Stat inc count (9) Output (non-polled)
22-Net Blr 5 Status blr13stat_13
AV:10 data float 142 nvoNetBlr5Stat inc count (9) Output (non-polled)
30030/128
23-Net Blr 6 Status blr14stat_13
AV:11 data float 143 nvoNetBlr6Stat inc count (9) Output (non-polled)
24-Net Blr 7 Status blr15stat_13
AV:12 data float 144 nvoNetBlr7Stat inc count (9) Output (non-polled)
30032/128
25-Net Blr 8 Status blr16stat_13
AV:13 data float 145 nvoNetBlr8Stat inc count (9) Output (non-polled)