USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
VD2:011712
1
GF-129
Equipment Point Name Name
Read
Only
BACnet Type:ID N2 Type N2 ID Lon SNVT NAME Lon SNVT Lon Direction
ModBus/Unit
Address
Blr Addr 10
01-Fire Rate Out boilerstate_10
AV:130 data float 91 nvoBlrState10 inc count (9) Output (non-polled)
30009/10
02-Active Setpoint effectsetpt_10
AV:131 data float 92 nvoEffSetpt10 inc count (9) Output (non-polled)
30017/10
03-Net Remote Setpt setpt_10 AV:132 data float 93 nviSetpt10 inc count (9) Input (non-polling)
40001/10
05-Fire Rate In boilerload_10
AV:124 data float 95 nvoBlrLoad10 inc count (9) Output (non-polled)
30018/10
06-Outlet Temp localsuptemp_10
AV:125 data float 96 nvoLocSupTmp10 inc count (9) Output (non-polled)
30003/10
07-Display Code dispcode_10
AV:126 data float 97 nvoDispCode10 inc count (9) Output (non-polled)
30001/10
08-Unit Status unitstat_10
AV:127 data float 98 nvoUnitStat10 inc count (9) Output (non-polled)
30002/10
09-Run Cycles runcycles_10
AV:128 data float 99 nvoRunCycles10 51 Output (non-polled)
30012-30013/10
10-Run Hours runhours_10
AV:129 data float 100 nvoRunHours10 51 Output (non-polled)
30014-30015/10
Blr Addr 11
01-Fire Rate Out boilerstate_11
AV:140 data float 101 nvoBlrState11 inc count (9) Output (non-polled)
30009/11
02-Active Setpoint effectsetpt_11
AV:141 data float 102 nvoEffSetpt11 inc count (9) Output (non-polled)
30017/11
03-Net Remote Setpt setpt_11 AV:142 data float 103 nviSetpt11 inc count (9) Input (non-polling)
40001/11
05-Fire Rate In boilerload_11
AV:134 data float 105 nvoBlrLoad11 inc count (9) Output (non-polled)
30018/11
06-Outlet Temp localsuptemp_11
AV:135 data float 106 nvoLocSupTmp11 inc count (9) Output (non-polled)
30003/11
07-Display Code dispcode_11
AV:136 data float 107 nvoDispCode11 inc count (9) Output (non-polled)
30001/11
08-Unit Status unitstat_11
AV:137 data float 108 nvoUnitStat11 inc count (9) Output (non-polled)
30002/11
09-Run Cycles runcycles_11
AV:138 data float 109 nvoRunCycles11 51 Output (non-polled)
30012-30013/11
10-Run Hours runhours_11
AV:139 data float 110 nvoRunHours11 51 Output (non-polled)
30014-30015/11
Blr Addr 12
01-Fire Rate Out boilerstate_12
AV:150 data float 111 nvoBlrState12 inc count (9) Output (non-polled)
30009/12
02-Active Setpoint effectsetpt_12
AV:151 data float 112 nvoEffSetpt12 inc count (9) Output (non-polled)
30017/12
03-Net Remote Setpt setpt_12 AV:152 data float 113 nviSetpt12 inc count (9) Input (non-polling)
40001/12
05-Fire Rate In boilerload_12
AV:144 data float 115 nvoBlrLoad12 inc count (9) Output (non-polled)
30018/12
06-Outlet Temp localsuptemp_12
AV:145 data float 116 nvoLocSupTmp12 inc count (9) Output (non-polled)
30003/12
07-Display Code dispcode_12
AV:146 data float 117 nvoDispCode12 inc count (9) Output (non-polled)
30001/12
08-Unit Status unitstat_12
AV:147 data float 118 nvoUnitStat12 inc count (9) Output (non-polled)
30002/12
09-Run Cycles runcycles_12
AV:148 data float 119 nvoRunCycles12 51 Output (non-polled)
30012-30013/12
10-Run Hours runhours_12
AV:149 data float 120 nvoRunHours12 51 Output (non-polled)
30014-30015/12
C.2.3 - Twelve C-Mores and One ACS/BMS II/BMS (Cont.)