Page 9 of 64
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288 VD2:011712
GF-129
2.3.3.1 ProtoNode RER: S0 – S3 (and A1*) DIP Switch Configuration Settings
S0 S1 S2 S3 A1* Profile
Off Off Off Off Off BACnet/IP/BACnet MS/TP, 1 ACS/BMS II/BMS, 4 C-More Controlled Boilers
On
Off Off Off Off BACnet/IP/BACnet MS/TP, 1 ACS/BMS II/BMS, 8 C-More Controlled Boilers
Off
On
Off Off Off BACnet/IP/BACnet MS/TP, 1 ACS/BMS II/BMS, 12 C-More Controlled Boilers
On On
Off Off Off BACnet/IP/BACnet MS/TP, 1 ACS/BMS II, 4 Modulex Boilers With BCMs
Off Off
On
Off Off BACnet/IP/BACnet MS/TP, 4 ECS/SP Systems
On
Off
On
Off Off BACnet/IP/BACnet MS/TP, 12 C-More, 6 ECS/SP, 4 Modulex and 2 ACS/BMS II
Off
On On
Off Off Metasys N2, 1 ACS/BMS II/BMS, 4 C-More Controlled Boilers
On On On
Off Off Metasys N2, 1 ACS/BMS II/BMS, 8 C-More Controlled Boilers
Off Off Off
On
Off Metasys N2, 1 ACS/BMS II/BMS CS, 12 C-More Controlled Boilers
On
Off Off
On
Off Metasys N2, 1 ACS/BMS II, 4 Modulex Boilers with BCMs
Off
On
Off
On
Off Metasys N2, 4 ECS/SP Systems
On On
Off
On
Off Metasys N2, 12 C-More, 6 ECS/SP, 4 Modulex and 2 ACS/BMS II
Off Off
On On
Off Modbus TCP, 1 ACS/BMS II/BMS, 4 C-More Controlled Boilers
On
Off
On On
Off Modbus TCP, 1 ACS/BMS II/BMS, 8 C-More Controlled Boilers
Off
On On On
Off Modbus TCP, 1 ACS/BMS II/BMS, 12 C-More Controlled Boilers
On On On On
Off Modbus TCP, 1 ACS/BMS II, 4 Modulex Boilers With BCMs
Off Off Off Off
On
Modbus TCP, 4 ECS/SP Systems
On
Off Off Off
On
Modbus TCP, 12 C-More, 6 ECS/SP, 4 Modulex and 2 ACS/BMS II
*NOTE:
The first sixteen profiles in the chart above (Section 2.3.3.1) require that DIP
switches A1 through A8 be set to OFF, which is the default setting, so those
switches do not need to be accessed for those configurations (and so are not
shown in the above chart). However, the last two profiles do require that DIP
switch A1 be set to ON, so for those two profiles, DIP Switch A1 needs to be
changed to ON (A2 through A8 remain in the OFF position).
A photograph showing the DIP switch locations inside the unit is on the next page.