USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288 VD2:011712
1
GF-129
B0 B1 B2 B3
Figure 2. B0 B3 DIP Switches
2.3.2.1 Baud Rate DIP Switch Selection
Baud B0 B1 B2 B3
Auto
Off
Off
Off
Off
9600
On
On
On
Off
19200
Off
Off
Off
On
38400
On
On
Off
On
57600
Off
Off
On
On
76800
On
Off
On
On
2.3.3 Using S0 S3 bank of DIP Switches to select and load Configuration Files
The S bank of DIP switches, S0 - S3 is used to select and load a configuration file from a group of
pretested/preloaded configuration files which are stored in the ProtoNode RER (BACnet MS/TP,
BACnet/IP, Modbus TCP and/or Metasys N2) and LER (LonWorks).
S0 S1 S2 S3
Figure 3. S0 S3 DIP Switches