Aerco ProtoNode Gateway Rev 1 (with internal LEDs) Manual de usuario Pagina 42

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 64
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 41
Page 42 of 64
USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
VD2:011712
1
GF-129
Equipment Point Name Name
Read
Only
BACnet Type:ID N2 Type N2 ID Lon SNVT NAME Lon SNVT Lon Direction
ModBus/Unit
Address
Blr Addr 7
01-Fire Rate Out boilerstate_7
AV:100 data float 61 nvoBlrState7 inc count (9) Output (non-polled)
30009/7
02-Active Setpoint effectsetpt_7
AV:101 data float 62 nvoEffSetpt7 inc count (9) Output (non-polled)
30017/7
03-Net Remote Setpt setpt_7 AV:102 data float 63 nviSetpt7 inc count (9) Input (non-polling)
40001/7
05-Fire Rate In boilerload_7
AV:94 data float 65 nvoBlrLoad7 inc count (9) Output (non-polled)
30018/7
06-Outlet Temp localsuptemp_7
AV:95 data float 66 nvoLocSupTmp7 inc count (9) Output (non-polled)
30003/7
07-Display Code dispcode_7
AV:96 data float 67 nvoDispCode7 inc count (9) Output (non-polled)
30001/7
08-Unit Status unitstat_7
AV:97 data float 68 nvoUnitStat7 inc count (9) Output (non-polled)
30002/7
09-Run Cycles runcycles_7
AV:98 data float 69 nvoRunCycles7 51 Output (non-polled)
30012-30013/7
10-Run Hours runhours_7
AV:99 data float 70 nvoRunHours7 51 Output (non-polled)
30014-30015/7
Blr Addr 8
01-Fire Rate Out boilerstate_8
AV:110 data float 71 nvoBlrState8 inc count (9) Output (non-polled)
30009/8
02-Active Setpoint effectsetpt_8
AV:111 data float 72 nvoEffSetpt8 inc count (9) Output (non-polled)
30017/8
03-Net Remote Setpt setpt_8 AV:112 data float 73 nviSetpt8 inc count (9) Input (non-polling)
40001/8
05-Fire Rate In boilerload_8
AV:104 data float 75 nvoBlrLoad8 inc count (9) Output (non-polled)
30018/8
06-Outlet Temp localsuptemp_8
AV:105 data float 76 nvoLocSupTmp8 inc count (9) Output (non-polled)
30003/8
07-Display Code dispcode_8
AV:106 data float 77 nvoDispCode8 inc count (9) Output (non-polled)
30001/8
08-Unit Status unitstat_8
AV:107 data float 78 nvoUnitStat8 inc count (9) Output (non-polled)
30002/8
09-Run Cycles runcycles_8
AV:108 data float 79 nvoRunCycles8 51 Output (non-polled)
30012-30013/8
10-Run Hours runhours_8
AV:109 data float 80 nvoRunHours8 51 Output (non-polled)
30014-30015/8
Blr Addr 9
01-Fire Rate Out boilerstate_9
AV:120 data float 81 nvoBlrState9 inc count (9) Output (non-polled)
30009/9
02-Active Setpoint effectsetpt_9
AV:121 data float 82 nvoEffSetpt9 inc count (9) Output (non-polled)
30017/9
03-Net Remote Setpt setpt_9 AV:122 data float 83 nviSetpt9 inc count (9) Input (non-polling)
40001/9
05-Fire Rate In boilerload_9
AV:114 data float 85 nvoBlrLoad9 inc count (9) Output (non-polled)
30018/9
06-Outlet Temp localsuptemp_9
AV:115 data float 86 nvoLocSupTmp9 inc count (9) Output (non-polled)
30003/9
07-Display Code dispcode_9
AV:116 data float 87 nvoDispCode9 inc count (9) Output (non-polled)
30001/9
08-Unit Status unitstat_9
AV:117 data float 88 nvoUnitStat9 inc count (9) Output (non-polled)
30002/9
09-Run Cycles runcycles_9
AV:118 data float 89 nvoRunCycles9 51 Output (non-polled)
30012-30013/9
10-Run Hours runhours_9
AV:119 data float 90 nvoRunHours9 51 Output (non-polled)
30014-30015/9
C.2.3 - Twelve C-Mores and One ACS/BMS II/BMS (Cont.)
Vista de pagina 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 63 64

Comentarios a estos manuales

Sin comentarios