C.2 BACnet/IP, BACnet MS/TP, Metasys N2, and LonWorks Points List
C.2.1 - Four C-Mores and One ACS/BMS II/BMS
Equipment Point Name Name Read Only
BACnet Type:ID
N2 Type N2 ID
Lon SNVT NAME
Lon SNVT Lon Direction ModBus/Unit Addr.
Blr Addr 1
01-Fire Rate Out boilerstate_1
AV:26 data float
1 nvoBlrState1 inc count (9)
Output (non-polled)
30009/1
02-Active Setpoint effectsetpt_1
AV:27 data float
2 nvoEffSetpt1 inc count (9)
Output (non-polled)
30017/1
03-Net Remote Setpt
setpt_1
AV:24
data float
3
nviSetpt1
inc count (9)
Input (non-polling)
40001/1
05-Fire Rate In
boilerload_1
AV:28
data float
5
nvoBlrLoad1
inc count (9)
Output (non-polled)
30018/1
06-Outlet Temp
localsuptemp_1
AV:29
data float
6
nvoLocSupTmp1
inc count (9)
Output (non-polled)
30003/1
07-Display Code dispcode_1
AV:22 data float
7 nvoDispCode1 inc count (9)
Output (non-polled)
30001/1
08-Unit Status unitstat_1
AV:23 data float
8 nvoUnitStat1 inc count (9)
Output (non-polled)
30002/1
09-Run Cycles runcycles_1
AV:42 data float
9 nvoRunCycles1 51 Output (non-polled)
30012-30013/1
10-Run Hours runhours_1
AV:43 data float
10 nvoRunHours1 51 Output (non-polled)
30014-30015/1
Blr Addr 2
01-Fire Rate Out boilerstate_2
AV:30 data float
11 nvoBlrState2 inc count (9)
Output (non-polled)
30009/2
02-Active Setpoint effectsetpt_2
AV:46 data float
12 nvoEffSetpt2 inc count (9)
Output (non-polled)
30017/2
03-Net Remote Setpt setpt_2 AV:47 data float
13 nviSetpt2 inc count (9)
Input (non-polling)
40001/2
05-Fire Rate In boilerload_2
AV:50 data float
15 nvoBlrLoad2 inc count (9)
Output (non-polled)
30018/2
06-Outlet Temp localsuptemp_2
AV:51 data float
16 nvoLocSupTmp2
inc count (9)
Output (non-polled)
30003/2
07-Display Code dispcode_2
AV:52 data float
17 nvoDispCode2 inc count (9)
Output (non-polled)
30001/2
08-Unit Status unitstat_2
AV:53 data float
18 nvoUnitStat2 inc count (9)
Output (non-polled)
30002/2
09-Run Cycles runcycles_2
AV:44 data float
19 nvoRunCycles2 51 Output (non-polled)
30012-30013/2
10-Run Hours runhours_2
AV:45 data float
20 nvoRunHours2 51 Output (non-polled)
30014-30015/2
Blr Addr 3
01-Fire Rate Out boilerstate_3
AV:54 data float
21 nvoBlrState3 inc count (9)
Output (non-polled)
30009/3
02-Active Setpoint effectsetpt_3
AV:55 data float
22 nvoEffSetpt3 inc count (9)
Output (non-polled)
30017/3
03-Net Remote Setpt setpt_3 AV:56 data float
23 nviSetpt3 inc count (9)
Input (non-polling)
40001/3
05-Fire Rate In boilerload_3
AV:60 data float
25 nvoBlrLoad3 inc count (9)
Output (non-polled)
30018/3