
Page 38 of 64
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
GF-129
Equipment Point Name Name
Read
BACnet Type:ID N2 Type N2 ID Lon SNVT NAME Lon SNVT Lon Direction
ModBus/Unit
02-Active Setpoint effectsetpt_6
AV:91 data float 52 nvoEffSetpt6 inc count (9) Output (non-polled)
03-Net Remote Setpt setpt_6 AV:92 data float 53 nviSetpt6 inc count (9) Input (non-polling)
40001/6
05-Fire Rate In boilerload_6
AV:84 data float 55 nvoBlrLoad6 inc count (9) Output (non-polled)
06-Outlet Temp localsuptemp_6
AV:85 data float 56 nvoLocSupTmp6 inc count (9) Output (non-polled)
30003/6
07-Display Code dispcode_6
AV:86 data float 57 nvoDispCode6 inc count (9) Output (non-polled)
08-Unit Status unitstat_6
AV:87 data float 58 nvoUnitStat6 inc count (9) Output (non-polled)
30002/6
09-Run Cycles runcycles_6
AV:88 data float 59 nvoRunCycles6 51 Output (non-polled)
10-Run Hours runhours_6
AV:89 data float 60 nvoRunHours6 51 Output (non-polled)
30014-30015/6
Blr Addr 7
01-Fire Rate Out boilerstate_7
AV:100 data float 61 nvoBlrState7 inc count (9) Output (non-polled)
30009/7
02-Active Setpoint effectsetpt_7
AV:101 data float 62 nvoEffSetpt7 inc count (9) Output (non-polled)
03-Net Remote Setpt setpt_7 AV:102 data float 63 nviSetpt7 inc count (9) Input (non-polling)
40001/7
05-Fire Rate In boilerload_7
AV:94 data float 65 nvoBlrLoad7 inc count (9) Output (non-polled)
06-Outlet Temp localsuptemp_7
AV:95 data float 66 nvoLocSupTmp7 inc count (9) Output (non-polled)
30003/7
07-Display Code dispcode_7
AV:96 data float 67 nvoDispCode7 inc count (9) Output (non-polled)
08-Unit Status unitstat_7
AV:97 data float 68 nvoUnitStat7 inc count (9) Output (non-polled)
30002/7
09-Run Cycles runcycles_7
AV:98 data float 69 nvoRunCycles7 51 Output (non-polled)
10-Run Hours runhours_7
AV:99 data float 70 nvoRunHours7 51 Output (non-polled)
30014-30015/7
Blr Addr 8
01-Fire Rate Out boilerstate_8
AV:110 data float 71 nvoBlrState8 inc count (9) Output (non-polled)
30009/8
02-Active Setpoint effectsetpt_8
AV:111 data float 72 nvoEffSetpt8 inc count (9) Output (non-polled)
03-Net Remote Setpt setpt_8 AV:112 data float 73 nviSetpt8 inc count (9) Input (non-polling)
40001/8
05-Fire Rate In boilerload_8
AV:104 data float 75 nvoBlrLoad8 inc count (9) Output (non-polled)
06-Outlet Temp localsuptemp_8
AV:105 data float 76 nvoLocSupTmp8 inc count (9) Output (non-polled)
30003/8
07-Display Code dispcode_8
AV:106 data float 77 nvoDispCode8 inc count (9) Output (non-polled)
08-Unit Status unitstat_8
AV:107 data float 78 nvoUnitStat8 inc count (9) Output (non-polled)
30002/8
09-Run Cycles runcycles_8
AV:108 data float 79 nvoRunCycles8 51 Output (non-polled)
10-Run Hours runhours_8
AV:109 data float 80 nvoRunHours8 51 Output (non-polled)
30014-30015/8
BMS Addr 128
01-Fire Rate Out boilerstate_13
AV:31 data float 121 nvoBlrState inc count (9) Output (non-polled)
30005/128
02-Header Set Temp effectsetpt_13
AV:32 data float 122 nvoEffSetpt inc count (9) Output (non-polled)
setpt_13 AV:33 data float 123 nviSetpt inc count (9) Input (non-polling)
C.2.2 - Eight C-Mores and One ACS/BMS II/BMS (Cont.)
Comentarios a estos manuales