E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 10: E8, BCM, AND BMM FAULT CODES
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 101 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
10.2.1 E8 Controller Fault Code Table
The table below lists the fault codes and fault descriptions associated with the E8 Controller.
Table 10-1: E8 Controller Fault Codes
Supplier low gas pressure
Flame absence during ignition time
Flame absence during operation time
High temperature on element (> 203°F)
Low water pressure (only with SensorLogic)
Flame presence before ignition cycle
Local flow sensor failure
Auxiliary sensor failure (DHW)
Global return sensor failure
Difference between global return sensor and local flow sensor > 86°F (rp +10)
Low temperature: risk of freeze
Flame present after burner shut off
Air pressure switch does not close within 30 sec. in the ignition cycle
Air pressure switch always active
Fan out of control: doesn’t achieve correct speed within 30 sec. of ignition cycle start
Fan out of control: does not stop within 30 sec. from the stop of the burner
Air pressure switch fault during the ignition time
Parameters setting alteration
Electrical supply < 108 VAC
Low system flow rate (only with SensorLogic)
Presence of air in the pump (only with SensorLogic)
Pump blocked (only with SensorLogic)
Pump wire failure (only with SensorLogic)
System Manager Fault – Sensor Defective (break/short circuit)
E8: F11 – flow sensor HC1
E8: F1 – buffer storage tank low sensor
E8: F3 – buffer storage tank top sensor
E8: F6 – storage tank sensor
E8: F15 – room sensor HC2
F12: HW Storage Tank Low Sensor, Multi-Function 2
F13: (PT1000): HS2, Collector 2, Multi-Function 3
F14: (PT1000): Collector 1, Multi-Function 4
F15 – room temperature HC2