CHAPTER 9: BCM MODBUS AND ADDRESS ASSIGNMENTS
Page 94 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
Table 9-4: BCM Standard Holding Register Address Mapping (Continued)
Menu Item Units and Range
Default
CONTROL REGISTERS (Continued)
1041
Check Mode,
Inserted burner
control
(0 – 0xFF)
Bit 0: BMM #0 to
(Read/Write)
Bit 0 (BMM #0) is
auto-
matically set at
Check Mode start
0 Error Code
of fault device:
0: BMM #0 to
7: BMM #7
(Read Only)
1000
Cascade Control
Status
Slave identification
procedure
(Read Only)
1002
Flow Sensor
Temperature
(-10°C to 100°C)
(Read Only)
1003
32°F to 212°F (0°C to 100°C)
(Value x 10)
1005
External Sensor
Temperature
(-35°C/-30°C to 30°C)
-31°F (-35°C) if not
1008
Global Actual
Modulation Level
1016
Actual Target
Setpoint
32°F to 212°F (0°C to 100°C)
(Value x 10)
Should increase up to “Target
Setpoint” temp as boiler heats up
(Read Only)
1018 Target Setpoint
32°F to 212°F (0°C to 100°C)
(Value x 10)
1019
32°F to 212°F (0°C to 100°C)
(Value x 10)