E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 8: BOILER COMMUNICATION MODULE (BCM)
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 87 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
Figure 8-11 shows a Sample Modbus Network wiring diagram for a Master EMS/BAS controlling
BCM Controller Slaves. This Figure shows an EMS or BAS Master equipped with a RS485 port.
If the EMS or BAS contains a 4-Wire RS485 port, refer to Detail “A” for wiring details. If the
controlling Master EMS/BAS contains only a RS232 port, a RS232-to-RS485 converter will be
required to interface with connector Y2 at each BCM Controller. It should be noted that this
diagram is only intended as a guide and does not include all possible scenarios. Refer to the
EMS/BAS manufacturer’s manual prior to attempting any network wiring connections.
Figure 7-11. EMS/BAS Master Controlling Modulex Boiler Slaves
TO OTHER NETWORK
BOILER SLAVES (3 - 9)
(SEE NOTE 3)
EMS MASTER
T+/R+
T-/R-
RS485 PORT
SHIELD
+
Y2-2 – MODBUS “A” (-)
(PART OF BCM CONN. Y2)
MODULEX BOILER SLAVE #1
NOTES:
1. IF EMS MASTER CONTAINS A 4-WIRE RS485 PORT,
TIE THE TWO POSITIVE (+) AND NEGATIVE (-)
LEADS TOGETHER AS SHOWN IN DETAIL “A”
2. IF EMS MASTER CONTAINS ONLY A RS232
PORT, A RS232-TO-RS485 CONVERTER WILL BE
REQUIRED.
3. THE LAST BCM SLAVE ON THE RS485 LOOP
MUST HAVE ITS TERMINATION RESISTOR
ENABLED. ALSO, A 1K OHM BIAS RESISTOR
MAY BE REQUIRED. CHECK WITH THE EMS
MANUFACTURER.
SEE NOTES 1 & 2
DETAIL “A”
(SEE NOTE 1)
T+
T-
4-WIRE RS485 PORT
SHIELD
R+
R-
T+/R+
T-/R-
Y2-1 – MODBUS “B” (+)
BCM
+
Y2-2 – MODBUS “A” (-)
(PART OF BCM CONN. Y2)
MODULEX BOILER SLAVE #2
Y2-1 – MODBUS “B” (+)
BCM
Figure 8-11: EMS/BAS Master Controlling Modulex Boiler Slaves