E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 9: BCM MODBUS AND ADDRESS ASSIGNMENTS
Page 98 of 108 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
Table 9-4: BCM Standard Holding Register Address Mapping (Continued)
Modbus Data
Address
Menu Item Units and Range
Default
(Comments)
TEST REGISTER (Continued)
3100
Digital Inputs Status
[0, 1]
Flags (0 - 0x1F80)
bit 0:
eBUS RX
bit 1:
eBUS-1 RX
bit 2:
eBUS -1 detect (true,
false)
bit 7:
Room Stat (open,
close)
bit 8:
0, not used
bit 9:
RESET by Low
Voltage Detector
bit 10:
RESET by clock
monitor
bit 11:
RESET by Watchdog
timer
bit 12:
RESET (open, close)
bit 13:
SW1-1
bit 14:
SW1-2
bit 15:
SW1-4
(Read Only)
3101
Digital Outputs
Status [0, 1]
Flags (0 - 0x0F)
bit 0:
Burner [OFF, ON]
bit 1:
Pump [OFF, ON]
bit 2:
Not used
Bit 3;
Alarm [OFF, ON]
bit 4:
DL1 [OFF, ON]
bit 5:
eBUS TX
bit 6:
eBUS-1 TX
bit 7:
eBUS Supply [OFF,
ON]
(Read Only)
3102
Digital Output
Control in Test
Mode [0, 1]
Flags (0 - 0x0F)
bit 0:
Not used
bit 1:
Pump [OFF, ON]
bit 2:
MPump-PWM
[100%, 0%]
bit 3;
Alarm [OFF, ON]
bit 4:
DL1 [OFF, ON]
bit 5:
eBUS TX
bit 6:
eBUS-1 TX
bit 7:
eBUS Supply [OFF,
ON]
(Read/Write)