E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
OMM-0093_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 43 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
Table 5-4: EXPERT Menu Listing (Continued)
FUNCTION DESCRIPTION
ENTRY
RANGE
DEFAULT
INSTALLATION Sub-Menu
(Continued)
SEQU CHANGE
Sequence change mode
01 06
06
SEQ SW TIME
Time to sequence change (hours)
10 800
200
LOCK TIME
Not Applicable
00 min 30 min
00
HYST BURNER2
Not Applicable
----
----
HS COOL-FCT Not Applicable ---- ----
T-HS COOL
Not Applicable
----
----
HEATSOURCE 1
Identification of Boiler Type being used:
00 = No Boiler
01 = Single-Stage, switching
02 = Single-Stage, modulating
03 = 2-Stage, switching
04 = 2 individual, switching
05 = Multi-Stage, switching
06 = Multi-Stage, modulating (cascade via BUS)
See
DESCRIPTION
06
(Multi-Stage
Modulating)
HS 1 BUS
Communication connection between Controller and
Heat Source
00 04 02
HEATSOURCE 2
Not Applicable
N/A
N/A
STORAGE HS2
Not Applicable
N/A
N/A
BUFFER
Not Applicable
N/A
N/A
SCREED
Not Applicable
N/A
N/A
SCREED PROGR
Not Applicable
N/A
N/A
RETURN
Press Program Key to exit INSTALLATION Sub-Menu.
HOT WATER Sub-Menu
DHW RELIEF
Not Applicable
N/A
N/A
PARALLEL
Parallel pump operation.
00 = Hot Water Priority
01 = Hot Water Partial Priority
02 = Pump Parallel Running
00, 01, 02
01
T-BOILER DHW
Boiler temperature increase during Hot Water
operation.
Boiler Temp = (DHW Temp Setting) + (T-BOILER
DHW)
32°F 194°F 97°F
HYST DHW
Hot Water Hysteresis
48°F129°F
48°F
DHW FOLLOWUP Pump Run-Down Time
00 min. 30
min.
00 min.
THERM INPUT
Storage Tank With Sensor = 00
Storage Tank With Thermostat = 01
00, 01
00 (Off)
WALL HUNG
Not Applicable
00 (Off)
LOAD THROUGH
Not Applicable
00 (Off)
RETURN
Press Program Key to exit HOT WATER Sub-Menu.
EXPERT EXPERT