CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 45 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
Table 5-4: EXPERT Menu Listing (Continued)
FUNCTION DESCRIPTION
DEFAULT
MF (1-4)
Not Applicable
MF (1-4)
Not Applicable
MF (1-4)
Not Applicable
F15 FUNCTION
F15 Function
00 = Room Sensor for Heating Circuit 2
01 = 0 – 10V iInput
00-02 00
RETURN
Press Program Key to exit SOLAR M/F
5.4.1 Available V-Curve Preset Voltage Curves for 0 – 10 Volt Input
The following listing (Table 5-4) shows the available preset V-Curve settings for operation in
the 0 to 10 Volt Mode:
Table 5-5: V-Curve Preset Voltage Curves for 0 – 10 Volt Input
CURVE NO. U1 U2 T1 T2 UO
0 2.0 V 10.0 V 32°F 194°F 2.0 V
1 2.5 V 0.3 V 100°F 176°F 5.0 V
2 2.5 V 0.3 V 100°F 167°F 5.0 V
3 2.5 V 0.3 V 100°F 113°F 5.0 V
4 4.0 V 0.1 V 68°F 185°F 5.0 V
5 4.0 V 0.1 V 68°F 167°F 5.0 V
6 4.0 V 0.1 V 68°F 131°F 5.0 V
7 4.0 V 0.1 V 68°F 189°F 5.0 V
8 4.0 V 0.1 V 68°F 189°F 5.0 V
9 4.0 V 0.1 V 68°F 163°F 5.0 V
10 4.0 V 0.1 V 68°F 127°F 5.0 V
11 4.0 V 0.1 V 68°F 194°F 5.0 V