AERCO ProtoNode Gateway
User Manual
Page 108 of 126 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0080_0H
11/06/2014 Ph.: 800-526-0288 GF-129
Table C-7: Eight C-More Boilers/Heaters and BST/WHM Master
Equip Point Name Name
Read
BACnet
N2 Type
N2
Lon SNVT
Lon
Lon Direction
ModBus
3
Outlet Temp SMD_BAS_IP_HTR_03_[3] AV:503 Data Float 89
inc count (9) Output (non-polled) 30503
3
FFWD Temp SMD_BAS_IP_HTR_03_[4] AV:504 Data Float 90
inc count (9) Output (non-polled) 30504
3
Inlet Temp SMD_BAS_IP_HTR_03_[5] AV:505 Data Float 91
inc count (9) Output (non-polled) 30505
3
Exhaust Temp SMD_BAS_IP_HTR_03_[6] AV:506 Data Float 92
inc count (9) Output (non-polled) 30506
3
Air Temp SMD_BAS_IP_HTR_03_[7]
AV:507 Data Float 93
inc count (9) Output (non-polled) 30507
3
Flame Strength SMD_BAS_IP_HTR_03_[8]
AV:508 Data Float 94
inc count (9) Output (non-polled) 30508
3
Fire Rate In SMD_BAS_IP_HTR_03_[9] AV:509 Data Float 95
inc count (9) Output (non-polled) 30509
3
Fire Rate Out SMD_BAS_IP_HTR_03_[10] AV:510 Data Float 96
inc count (9) Output (non-polled) 30510
3
Unit Type SMD_BAS_IP_HTR_03_[11] AV:511 Data Float 97
inc count (9) Output (non-polled) 30511
3
Unit Size SMD_BAS_IP_HTR_03_[12] AV:512 Data Float 98
inc count (9) Output (non-polled) 30512
3
Value State SMD_BAS_IP_HTR_03_[13]
AV:513 Data Float 99
inc count (9) Output (non-polled) 30513
3
Net Remote Setpt SMD_BAS_IP_HTR_03_[14]
AV:514 Data Float 100
inc count (9) Output (non-polled) 30514
3
Run Cycles Upper SMD_BAS_IP_HTR_03_[15] AV:515 Data Float 101
inc count (9) Output (non-polled) 30515
3
Run Cycles Lower SMD_BAS_IP_HTR_03_[16] AV:516 Data Float 102
inc count (9) Output (non-polled) 30516
3
Run Hours Upper SMD_BAS_IP_HTR_03_[17] AV:517 Data Float 103
inc count (9) Output (non-polled) 30517
3
Run Hours Lower SMD_BAS_IP_HTR_03_[18] AV:518 Data Float 104
inc count (9) Output (non-polled) 30518
3
Oxygen Level SMD_BAS_IP_HTR_03_[19]
AV:519 Data Float 105
inc count (9) Output (non-polled) 30519
Blr Addr 4
4
Comm Address SMD_BAS_IP_HTR_04_[0] AV:600 Data Float 106
inc count (9) Output (non-polled) 30600
4
Unit Status SMD_BAS_IP_HTR_04_[1] AV:601 Data Float 107
inc count (9) Output (non-polled) 30601
4
Fault Code SMD_BAS_IP_HTR_04_[2] AV:602 Data Float 108
inc count (9) Output (non-polled) 30602
4
Outlet Temp SMD_BAS_IP_HTR_04_[3] AV:603 Data Float 109
inc count (9) Output (non-polled) 30603
4
FFWD Temp SMD_BAS_IP_HTR_04_[4]
AV:604 Data Float 110
inc count (9) Output (non-polled) 30604
4
Inlet Temp SMD_BAS_IP_HTR_04_[5]
AV:605 Data Float 111
inc count (9) Output (non-polled) 30605
4
Exhaust Temp SMD_BAS_IP_HTR_04_[6] AV:606 Data Float 112
inc count (9) Output (non-polled) 30606