AERCO ProtoNode Gateway
User Manual
Page 38 of 126 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0080_0H
11/06/2014 Ph.: 800-526-0288 GF-129
Step 3: Send Log
Click the “Send Log” button located near the bottom of the dialog. The following dialog
should appear.
Figure 7-4: Send Log Dialog Box
Push the ‘Locate Folder’ button to launch explorer and have it point directly at the correct
folder. The file upload.zip must be sent to
support@fieldserver.com.
Step 4: Close the Program
Press the exit button when the log is completed
7.3 Writing Setpoint to AERCO Devices
The administrator must setup their Building Automation System to write the Setpoint through the
gateway to the C-More, ACS or BMS II at least three times within the Network timeout. The
setpoint value to write is called “Net Remote Setpoint” in the C-More and “Net Header Set Point”
in the ACS and BMS II. See Point tables in Appendix B and C. See also Section 2.3.
Table 7-1: Timeout Values
AERCO Device Parameter
Default
Value
Range Menu
BMS II
Network Timeout 30 s 5 to 240 s RS-232
C-More
Network Timeout 30 s 5 to 999 s Configuration
ACS
Network Timeout 30 s 5 to 240 s RS-232
Refer to GF-112, GF-124, and GF-131 for more information.