Aerco ProtoNode Gateway Rev 3 (with external LEDs) Manual de usuario Pagina 93

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 126
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 92
AERCO ProtoNode Gateway
User Manual
OMM-0080_0H AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 93 of 126
GF-129 Ph.: 800-526-0288 11/06/2014
Table C-6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II
Equip Point Name Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon SNVT
Lon
Direction
ModBus/
Unit
Address
4
02-Target Setpoint effectsetpt_16
AV:152
data
float
152 nvoMlxSetpt16 inc count (9) Output (non-polled) 41019/16
4
03-Req Outlet
Temp
setpt_16 AV:153
data
float
153 nviMlxSetptRq16 inc count (9) Input (non-polling) 41005/16
4
04-Net Direct Drive boilercmd_4 AV:154
data
float
154 nviMlxCmd4 inc count (9) Input (non-polling) 40002/4
C-More Addr 5
5
01-Fire Rate Out boilerstate_5 AV:41
data
float
41 nvoBlrState5 inc count (9) Output (non-polled) 30009/5
5
02-Active Setpoint effectsetpt_5
AV:42
data
float
42 nvoEffSetpt5 inc count (9) Output (non-polled) 30017/5
5
03-Net Remote
Setpt
setpt_5
AV:43
data
float
43 nviSetpt5 inc count (9) Input (non-polling) 40001/5
5
05-Fire Rate In boilerload_5
AV:45
data
float
45 nvoBlrLoad5 inc count (9) Output (non-polled) 30018/5
5
06-Outlet Temp localsuptemp_5
AV:46
data
float
46 nvoLocSupTmp5 inc count (9) Output (non-polled) 30003/5
5
07-Display Code dispcode_5
AV:47
data
float
47 nvoDispCode5 inc count (9) Output (non-polled) 30001/5
5
08-Unit Status unitstat_5
AV:48
data
float
48 nvoUnitStat5 inc count (9) Output (non-polled) 30002/5
5
09-Run Cycles runcycles_5
AV:49
data
float
49 nvoRunCycles5 51 Output (non-polled)
30012-
30013/5
5
10-Run Hours runhours_5
AV:50
data
float
50 nvoRunHours5 51 Output (non-polled)
30014-
30015/5
C-More Addr 6
6
01-Fire Rate Out boilerstate_6
AV:51
data
float
51 nvoBlrState6 inc count (9) Output (non-polled) 30009/6
6
02-Active Setpoint effectsetpt_6
AV:52
data
float
52 nvoEffSetpt6 inc count (9) Output (non-polled) 30017/6
6
03-Net Remote
Setpt
setpt_6 AV:53
data
float
53 nviSetpt6 inc count (9) Input (non-polling) 40001/6
6
05-Fire Rate In boilerload_6 AV:55
data
float
55 nvoBlrLoad6 inc count (9) Output (non-polled) 30018/6
Vista de pagina 92