GF-129 Ph.: 800-526-0288 11/06/2014
Table C-2: Eight C-Mores and One ACS/BMS II/BMS
Equip Point Name Name
Lon SNVT Lon Direction
8 02-Active Setpoint effectsetpt_8
AV:111
72 nvoEffSetpt8 inc count (9) Output (non-polled) 30017/8
8 03-Net Remote Setpt setpt_8
AV:112
73 nviSetpt8 inc count (9) Input (non-polling) 40001/8
8 05-Fire Rate In boilerload_8 AV:104
75 nvoBlrLoad8 inc count (9) Output (non-polled) 30018/8
8 06-Outlet Temp
AV:105
76 nvoLocSupTmp8 inc count (9) Output (non-polled) 30003/8
8 07-Display Code dispcode_8
AV:106
77 nvoDispCode8 inc count (9) Output (non-polled) 30001/8
8 08-Unit Status unitstat_8
AV:107
78 nvoUnitStat8 inc count (9) Output (non-polled) 30002/8
8 09-Run Cycles runcycles_8 AV:108
79 nvoRunCycles8 51 Output (non-polled)
8 10-Run Hours runhours_8 AV:109
80 nvoRunHours8 51 Output (non-polled)
8 11-Oxygen o2level_8 AV:168
168 nvoO2Lev8 inc count (9) Output (non-polled) 30010/8
8 12-Exhaust Temp exhtemp_8
AV:188
188 nvoExhTmp8 inc count (9) Output (non-polled) 30007/8
BMS Addr 128
128 01-Fire Rate Out boilerstate_13 AV:31
121 nvoBlrState inc count (9) Output (non-polled) 30005/128
128 02-Header Set Temp effectsetpt_13 AV:32
122 nvoEffSetpt inc count (9) Output (non-polled) 30006/128
128
setpt_13
AV:33
123 nviSetpt inc count (9) Input (non-polling) 40005/128
128 04-Header Temp
AV:34
124 nvoLocSupTmp inc count (9) Output (non-polled) 30002/128
128 05-Outside Air Temp
AV:35
125 nvoLocOATmp inc count (9) Output (non-polled) 30003/128
128 06-Display Code dispcode_13 AV:36
126 nvoDispCode inc count (9) Output (non-polled) 30011/128