AERCO ProtoNode Gateway
User Manual
OMM-0080_0H AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 55 of 126
GF-129 Ph.: 800-526-0288 11/06/2014
Appendix B.1: AERCO C-More & ACS/BMS II/BMS Point Definitions (Cont.)
Point Name
BAS Modbus
Data Address
GF-108, GF-
124, GF-114
Point Name
Reg.
Type
Modbus
Data
Address
(Hex/Dec.)
Units (Range)
ACS/BMS II/BMS (Cont.)
06-Display Code 30011
Fault/Message
Code
Input 0x000A / 10
Bit (0 to 65535)
Bit 0 = Outside Air Sensor
Error
Bit 1 = Header Sensor Error
Bit 2 = Interlock 1 Error
Bit 3 = Interlock 2 Error
Bit 4 = Indoor Air/Return
Sens Error
Bit 5 = 4-20 mA Input Error
07-Num Boilers Fired 30008
Total Boilers
Fired
Input 0x0007 / 7
(0 to 40) BMS
(0 to 32) BMSII
08-Num Boilers Online 30009
Total Boilers On
Line
Input 0x0008 / 8
(0 to 40) BMS
(0 to 32) BMSII
09-Last Blr Fired 30017 Last Boiler Fired Input 0x0010 / 16
(1 to 40) BMS
(1 to 32) BMSII
10-Boiler 1 Status 30018
Boiler 1 Status
(PWM Boiler 1)
Input 0x0011 / 17
Enum (1 to 40, 119, 120)
1 to 40 = Fired and Sequence
119 = Not On Line
120 = On Line But Not Fired
11-Boiler 2 Status 30019
Boiler 2 Status
(PWM Boiler 2)
Input 0x0012 / 18 Same As Above
12-Boiler 3 Status 30020
Boiler 3 Status
(PWM Boiler 3)
Input 0x0013 / 19 Same As Above
13-Boiler 4 Status 30021
Boiler 4 Status
(PWM Boiler 4)
Input 0x0014 / 20 Same As Above
14-Boiler 5 Status 30022
Boiler 5 Status
(PWM Boiler 5)
Input 0x0015 / 21
Enum (1 to 40, 119, 120)
1 to 40 = Fired and
Sequence
119 = Not On Line
120 = On Line But Not
Fired
15-Boiler 6 Status 30023
Boiler 6 Status
(PWM Boiler 6)
Input 0x0016 / 22 Same As Above
16-Boiler 7 Status 30024
Boiler 7 Status
(PWM Boiler 7)
Input 0x0017 / 23 Same As Above
17-Boiler 8 Status 30025
Boiler 8 Status
(PWM Boiler 8)
Input 0x0018 / 24 Same As Above
18-Net Blr 1 Status 30026 Net Boiler 1 Input 0x0019 / 25
Enum (1 to 40, 119, 120)
1 to 40 = Fired and
Sequence
119 = Not On Line
120 = On Line But Not
Fired
121 = On Line But Disabled
122 = On Line But Faulted
19-Net Blr 2 Status 30027 Net Boiler 2 Input 0x001A / 26 Same As Above
20-Net Blr 3 Status 30028 Net Boiler 3 Input 0x001B / 27 Same As Above
21-Net Blr 4 Status 30029 Net Boiler 4 Input 0x001C / 28 Same As Above
22-Net Blr 5 Status 30030 Net Boiler 5 Input 0x001D / 29 Same As Above
23-Net Blr 6 Status 30031 Net Boiler 6 Input 0x001E / 30 Same As Above
24-Net Blr 7 Status 30032 Net Boiler 7 Input 0x001F / 31 Same As Above