AERCO ProtoNode Gateway
User Manual
Page 96 of 126 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0080_0H
11/06/2014 Ph.: 800-526-0288 GF-129
Table C-6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II
Equip Point Name Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon SNVT
Lon
Direction
ModBus/
Unit
Address
10
01-Fire Rate Out boilerstate_10
AV:91
data
float
91 nvoBlrState10 inc count (9) Output (non-polled) 30009/10
10
02-Active Setpoint effectsetpt_10
AV:92
data
float
92 nvoEffSetpt10 inc count (9) Output (non-polled) 30017/10
10
03-Net Remote
Setpt
setpt_10
AV:93
data
float
93 nviSetpt10 inc count (9) Input (non-polling) 40001/10
10
05-Fire Rate In boilerload_10
AV:95
data
float
95 nvoBlrLoad10 inc count (9) Output (non-polled) 30018/10
10
06-Outlet Temp
localsuptemp_1
0
AV:96
data
float
96 nvoLocSupTmp10 inc count (9) Output (non-polled) 30003/10
10
07-Display Code dispcode_10
AV:97
data
float
97 nvoDispCode10 inc count (9) Output (non-polled) 30001/10
10
08-Unit Status unitstat_10
AV:98
data
float
98 nvoUnitStat10 inc count (9) Output (non-polled) 30002/10
10
09-Run Cycles runcycles_10
AV:99
data
float
99 nvoRunCycles10 51 Output (non-polled)
30012-
30013/10
10
10-Run Hours runhours_10
AV:100
data
float
100 nvoRunHours10 51 Output (non-polled)
30014-
30015/10
C-More Addr 11
11
01-Fire Rate Out boilerstate_11
AV:101
data
float
101 nvoBlrState11 inc count (9) Output (non-polled) 30009/11
11
02-Active Setpoint effectsetpt_11
AV:102
data
float
102 nvoEffSetpt11 inc count (9) Output (non-polled) 30017/11
11
03-Net Remote
Setpt
setpt_11
AV:103
data
float
103 nviSetpt11 inc count (9) Input (non-polling) 40001/11
11
05-Fire Rate In boilerload_11
AV:105
data
float
105 nvoBlrLoad11 inc count (9) Output (non-polled) 30018/11
11
06-Outlet Temp
localsuptemp_1
1
AV:106
data
float
106 nvoLocSupTmp11 inc count (9) Output (non-polled) 30003/11
11
07-Display Code dispcode_11
AV:107
data
float
107 nvoDispCode11 inc count (9) Output (non-polled) 30001/11
11
08-Unit Status unitstat_11
AV:108
data
float
108 nvoUnitStat11 inc count (9) Output (non-polled) 30002/11