AERCO ProtoNode Gateway
User Manual
OMM-0080_0H AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 85 of 126
GF-129 Ph.: 800-526-0288 11/06/2014
Appendix C.4: Four Modulex and One ACS/BMS II
Table C-4: Four Modulex and One ACS/BMS II
Equip Point Name Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon SNVT Lon Direction
ModBus/Unit
Address
BMS Addr 128
128
01-Fire Rate Out boilerstate_5
AV:31
data
float
41 nvoBlrState inc count (9) Output (non-polled) 30005/128
128
02-Header Set
Temp
effectsetpt_5
AV:32
data
float
42 nvoEffSetpt inc count (9) Output (non-polled) 30006/128
128
03-Net Header Set
Temp
setpt_5
AV:33
data
float
43 nviSetpt inc count (9) Input (non-polling) 40005/128
128
04-Header Temp localsuptemp_5
AV:34
data
float
44 nvoLocSupTmp inc count (9) Output (non-polled) 30002/128
128
05-Outside Air
Temp
localoatemp_5
AV:35
data
float
45 nvoLocOATmp inc count (9) Output (non-polled) 30003/128
128
06-Display Code dispcode_5
AV:36
data
float
46 nvoDispCode inc count (9) Output (non-polled) 30011/128
128
07-Num Boilers
Fired
blrfired_5
AV:37
data
float
47 nvoBlrsFired inc count (9) Output (non-polled) 30008/128
128
08-Num Boilers
Online
blronline_5
AV:38
data
float
48 nvoBlrsOnline inc count (9) Output (non-polled) 30009/128
128
09-Last Blr Fired blrlast_5
AV:39
data
float
49 nvoLastBlrFired inc count (9) Output (non-polled) 30017/128
128
18-Net Blr 1 Status blr9stat_5
AV:26
data
float
58 nvoNetBlr1Stat inc count (9) Output (non-polled) 30026/128
128
19-Net Blr 2 Status blr10stat_5
AV:27
data
float
59 nvoNetBlr2Stat inc count (9) Output (non-polled) 30027/128
128
20-Net Blr 3 Status blr11stat_5
AV:47
data
float
60 nvoNetBlr3Stat inc count (9) Output (non-polled) 30028/128
128
21-Net Blr 4 Status blr12stat_5
AV:49
data
float
61 nvoNetBlr4Stat inc count (9) Output (non-polled) 30029/128
128 22-Return Temp localrettemp_5
AV:173
data
float
173 nvoLocRetTmp inc count (9) Output (non-polled)
30004/128
Mlx Addr 1
1
01-Act Mod Lev boilerstate_1
AV:134
data
float
62 nvoMlxState1 inc count (9) Output (non-polled) 41009/1