AERCO ProtoNode Gateway
User Manual
OMM-0080_0H AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 87 of 126
GF-129 Ph.: 800-526-0288 11/06/2014
Table C-4: Four Modulex and One ACS/BMS II
Equip Point Name Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon SNVT Lon Direction
ModBus/Unit
Address
2
08-Unit Status unitstat_2
AV:151
data
float
161 nvoMlxStat2 inc count (9) Output (non-polled) 30002/2
2
09-Ret Flow Temp returntemp_2
AV:5
data
float
162 nvoMlxRetTmp2 inc count (9) Output (non-polled) 41004/2
Mlx Addr 3
3
01-Act Mod Lev boilerstate_3
AV:18
data
float
164 nvoMlxState3 inc count (9) Output (non-polled) 41009/3
3
02-Target Setpoint effectsetpt_3
AV:19
data
float
165 nvoMlxSetpt3 inc count (9) Output (non-polled) 41019/3
3
03-Req Outlet
Temp
setpt_3 AV:20
data
float
166 nviMlxSetptRq3 inc count (9) Input (non-polling) 41005/3
3
04-Net Direct Drive boilercmd_3 AV:21
data
float
167 nviMlxCmd3 inc count (9) Input (non-polling) 40002/3
3
05-Mod Lev In boilerload_3
AV:22
data
float
168 nvoMlxLoad3 inc count (9) Output (non-polled) 41201/3
3
06-Flow Sens
Temp
localsuptemp_3
AV:23
data
float
169 nvoMlxSupTmp3 inc count (9) Output (non-polled) 41003/3
3
07-Display Code dispcode_3
AV:24
data
float
170 nvoMlxDispCode3 inc count (9) Output (non-polled) 30001/3
3
11-Error Code errcode_3
AV:7
data
float
171 nvoMlxErrCode3 51 Output (non-polled) 40001/3
3
08-Unit Status unitstat_3
AV:25
data
float
172 nvoMlxStat3 inc count (9) Output (non-polled) 30002/3
3
09-Ret Flow Temp returntemp_3
AV:8
data
float
173 nvoMlxRetTmp3 inc count (9) Output (non-polled)
41004/3
Mlx Addr 4
4
01-Act Mod Lev boilerstate_4
AV:28
data
float
175 nvoMlxState4 inc count (9) Output (non-polled) 41009/4
4
02-Target Setpoint effectsetpt_4
AV:29
data
float
176 nvoMlxSetpt4 inc count (9) Output (non-polled) 41019/4
4
03-Req Outlet
Temp
setpt_4 AV:30
data
float
177 nviMlxSetptRq4 inc count (9) Input (non-polling) 41005/4
4
04-Net Direct Drive boilercmd_4
AV:42
data
float
178 nviMlxCmd4 inc count (9) Input (non-polling) 40002/4