AERCO ProtoNode Gateway
User Manual
Page 68 of 126 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0080_0H
11/06/2014 Ph.: 800-526-0288 GF-129
Table C-2: Eight C-Mores and One ACS/BMS II/BMS
Equip Point Name Name
Lon SNVT Lon Direction
3 10-Run Hours runhours_3
AV:59
30 nvoRunHours3 51 Output (non-polled)
3 11-Oxygen o2level_3 AV:163
163 nvoO2Lev3 inc count (9) Output (non-polled) 30010/3
3 12-Exhaust Temp exhtemp_3 AV:183
183 nvoExhTmp3 inc count (9) Output (non-polled) 30007/3
Blr Addr 4
4 01-Fire Rate Out boilerstate_4
AV:70
31 nvoBlrState4 inc count (9) Output (non-polled) 30009/4
4 02-Active Setpoint effectsetpt_4
AV:71
32 nvoEffSetpt4 inc count (9) Output (non-polled) 30017/4
4 03-Net Remote Setpt setpt_4 AV:72
33 nviSetpt4 inc count (9) Input (non-polling) 40001/4
4 05-Fire Rate In boilerload_4 AV:73
35 nvoBlrLoad4 inc count (9) Output (non-polled) 30018/4
4 06-Outlet Temp
AV:65
36 nvoLocSupTmp4 inc count (9) Output (non-polled) 30003/4
4 07-Display Code dispcode_4
AV:66
37 nvoDispCode4 inc count (9) Output (non-polled) 30001/4
4 08-Unit Status unitstat_4
AV:67
38 nvoUnitStat4 inc count (9) Output (non-polled) 30002/4
4 09-Run Cycles runcycles_4 AV:68
39 nvoRunCycles4 51 Output (non-polled)
4 10-Run Hours runhours_4 AV:69
40 nvoRunHours4 51 Output (non-polled)
4 11-Oxygen o2level_4 AV:164
164 nvoO2Lev4 inc count (9) Output (non-polled) 30010/4
4 12-Exhaust Temp exhtemp_4
AV:184
184 nvoExhTmp4 inc count (9) Output (non-polled) 30007/4
Blr Addr 5
5 01-Fire Rate Out boilerstate_5 AV:80
41 nvoBlrState5 inc count (9) Output (non-polled) 30009/5
5 02-Active Setpoint effectsetpt_5 AV:81
42 nvoEffSetpt5 inc count (9) Output (non-polled) 30017/5