7.6 Troubleshooting Procedures for Connection Problems
Confirm that the network cabling is correct.
Confirm that the computer network card is operational and correctly configured.
Confirm that there is an Ethernet adapter installed in the PC’s Device Manager List, and
that it is configured to run the TCP/IP protocol.
Check that the IP netmask of the PC matches the ProtoNode. The Default IP Address of
the ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0
1) Go to Start > Run.
2) Type in “ipconfig”.
3) The account settings should be displayed.
4) Ensure that the IP address is 192.168.1.xxx and the netmask 255.255.255.0
Ensure that the PC and ProtoNode are on the same IP Network, or assign a Static IP
Address to the PC on the 192.168.1.0 network using the Remote User Interface Utility.
If Using Windows XP, ensure that the firewall is disabled.
Ensure that all other Ethernet cards active on the PC, especially wireless adapters are
disabled.
Refer to the Field Server Troubleshooting Guide which can be found at
www/protocessor.com/downloads/ under documentation.
Confirm that the network cabling is correct.
If write values are lost from time to time, check that the timeout values for the ACS, BMS II,
C-More and the host system are compatible. Refer to Section 4.5 in this manual for more
information.