AERCO ProtoNode Gateway
User Manual
Page 54 of 126 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0080_0H
11/06/2014 Ph.: 800-526-0288 GF-129
Appendix B: AERCO EQUIPMENT MONITOR AND CONTROL POINT
DEFINITIONS
Definitions of the monitor and control points associated with the AERCO Equipment
Configurations are provided in the tables which follow.
Appendix B.1: AERCO C-More & ACS/BMS II/BMS Point Definitions
Table B-1: AERCO C-More & ACS/BMS II/BMS Point Definitions
Point Name
BAS Modbus
Data Address
GF-108, GF-
124, GF-114
Point Name
Reg.
Type
Modbus Data
Address
(Hex/Dec.)
Units (Range)
C-More Boiler
01-Fire Rate Out
30009
Fire Rate Out
Input
0x0008 / 8
% (0 to 100)
02-Active Setpoint
30017
Active Set Point
Input
0x0010 / 16
deg F (40 to 220)
03-Net Remote Setpt 40001
Net Remote Set
Point
Holding 0x0000 / 0
deg F (40 to 220)
* 04-Net Direct Drive
40002
Net Direct
Drive
Holding 0x0001 / 1 % (0 to 100)
05-Fire Rate In
30018
Fire Rate In
Input
0x0011 / 17
% (0 to 100)
06-Outlet Temp
30003
Outlet Temp
Input
0x0002 / 2
deg F (30 to 245)
07-Display Code 30001
Default
Message
Display Code
Input 0x0000 / 0
Enum (1 to 48)
See Part III, Appendix
A
08-Unit Status 30002 Unit Status Input 0x0001 / 1
Enum (0 to 5)
0 = Disabled
1 = Standby
2 = Manual Operation
3 = Remote Operation
4 = Auto Operation
5 = Fault
09-Run Cycles 30012-30013 Run Cycles Input
0x000B - 0x000C
/ 11 - 12
(0 to 999,999)
10-Run Hours 30014-30015 Run Hours Input
0x000D - 0x000E
/ 13 - 14
(0 to 999,999)
11-Oxygen
30010
O2 Level
Input
0x0009 / 9
% (0 to 25)
12-Exhaust Temp
30007
Exhaust Temp
Input
0x0006 / 6
Deg F (50 to 550)
* Where available in special profiles
ACS/BMS II/BMS
01-Fire Rate Out
30005 Fire Rate Out Input 0x0004 / 4 % (0 to 100)
02-Header Set Temp 30006
Header Set
Temperature
Input 0x0005 / 5 °F (40 to 220)
03-Net Header Set Temp 40005
Net Header Set
Temp
Holding 0x0004 / 4 °F (40 to 220)
04-Header Temp 30002
Header
Temperature
Input 0x0001 / 1 °F (40 to 220)
05-Outside Air Temp 30003
Outside Air
Temperature
Input 0x0002 / 2 °F (-60 to 120)