Appendix B: AERCO EQUIPMENT MONITOR AND CONTROL POINT
DEFINITIONS
Definitions of the monitor and control points associated with the AERCO Equipment
Configurations are provided in the tables which follow.
Appendix B.1: AERCO C-More & ACS/BMS II/BMS Point Definitions
Table B-1: AERCO C-More & ACS/BMS II/BMS Point Definitions
Point Name
BAS Modbus
Data Address
124, GF-114
Reg.
Type
Address
Units (Range)
C-More Boiler
03-Net Remote Setpt 40001
Holding 0x0000 / 0
* 04-Net Direct Drive
40002
Holding 0x0001 / 1 % (0 to 100)
07-Display Code 30001
Message
Input 0x0000 / 0
See Part III, Appendix
08-Unit Status 30002 Unit Status Input 0x0001 / 1
0 = Disabled
1 = Standby
2 = Manual Operation
3 = Remote Operation
4 = Auto Operation
09-Run Cycles 30012-30013 Run Cycles Input
0x000B - 0x000C
/ 11 - 12
(0 to 999,999)
10-Run Hours 30014-30015 Run Hours Input
0x000D - 0x000E
/ 13 - 14
(0 to 999,999)
* Where available in special profiles
ACS/BMS II/BMS
01-Fire Rate Out
30005 Fire Rate Out Input 0x0004 / 4 % (0 to 100)
02-Header Set Temp 30006
Input 0x0005 / 5 °F (40 to 220)
03-Net Header Set Temp 40005
Holding 0x0004 / 4 °F (40 to 220)
04-Header Temp 30002
Input 0x0001 / 1 °F (40 to 220)
05-Outside Air Temp 30003
Input 0x0002 / 2 °F (-60 to 120)