AERCO ProtoNode Gateway
User Manual
OMM-0080_0H AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 111 of 126
GF-129 Ph.: 800-526-0288 11/06/2014
Table C-7: Eight C-More Boilers/Heaters and BST/WHM Master
Equip Point Name Name
Read
BACnet
N2 Type
N2
Lon SNVT
Lon
Lon Direction
ModBus
6
Run Cycles Upper SMD_BAS_IP_HTR_06_[15] AV:815 Data Float 161
inc count (9) Output (non-polled) 30815
6
Run Cycles Lower SMD_BAS_IP_HTR_06_[16] AV:816 Data Float 162
inc count (9) Output (non-polled) 30816
6
Run Hours Upper SMD_BAS_IP_HTR_06_[17] AV:817 Data Float 163
inc count (9) Output (non-polled) 30817
6
Run Hours Lower SMD_BAS_IP_HTR_06_[18] AV:818 Data Float 164
inc count (9) Output (non-polled) 30818
6
Oxygen Level SMD_BAS_IP_HTR_06_[19]
AV:819 Data Float 165
inc count (9) Output (non-polled) 30819
Blr Addr 7
7
Comm Address SMD_BAS_IP_HTR_07_[0] AV:900 Data Float 166
inc count (9) Output (non-polled) 30900
7
Unit Status SMD_BAS_IP_HTR_07_[1] AV:901 Data Float 167
inc count (9) Output (non-polled) 30901
7
Fault Code SMD_BAS_IP_HTR_07_[2] AV:902 Data Float 168
inc count (9) Output (non-polled) 30902
7
Outlet Temp SMD_BAS_IP_HTR_07_[3] AV:903 Data Float 169
inc count (9) Output (non-polled) 30903
7
FFWD Temp SMD_BAS_IP_HTR_07_[4]
AV:904 Data Float 170
inc count (9) Output (non-polled) 30904
7
Inlet Temp SMD_BAS_IP_HTR_07_[5]
AV:905 Data Float 171
inc count (9) Output (non-polled) 30905
7
Exhaust Temp SMD_BAS_IP_HTR_07_[6] AV:906 Data Float 172
inc count (9) Output (non-polled) 30906
7
Air Temp SMD_BAS_IP_HTR_07_[7] AV:907 Data Float 173
inc count (9) Output (non-polled) 30907
7
Flame Strength SMD_BAS_IP_HTR_07_[8] AV:908 Data Float 174
inc count (9) Output (non-polled) 30908
7
Fire Rate In SMD_BAS_IP_HTR_07_[9] AV:909 Data Float 175
inc count (9) Output (non-polled) 30909
7
Fire Rate Out SMD_BAS_IP_HTR_07_[10]
AV:910 Data Float 176
inc count (9) Output (non-polled) 30910
7
Unit Type SMD_BAS_IP_HTR_07_[11]
AV:911 Data Float 177
inc count (9) Output (non-polled) 30911
7
Unit Size SMD_BAS_IP_HTR_07_[12] AV:912 Data Float 178
inc count (9) Output (non-polled) 30912
7
Value State SMD_BAS_IP_HTR_07_[13] AV:913 Data Float 179
inc count (9) Output (non-polled) 30913
7
Net Remote Setpt SMD_BAS_IP_HTR_07_[14] AV:914 Data Float 180
inc count (9) Output (non-polled) 30914
7
Run Cycles Upper SMD_BAS_IP_HTR_07_[15] AV:915 Data Float 181
inc count (9) Output (non-polled) 30915
7
Run Cycles Lower SMD_BAS_IP_HTR_07_[16]
AV:916 Data Float 182
inc count (9) Output (non-polled) 30916
7
Run Hours Upper SMD_BAS_IP_HTR_07_[17]
AV:917 Data Float 183
inc count (9) Output (non-polled) 30917
7
Run Hours Lower SMD_BAS_IP_HTR_07_[18] AV:918 Data Float 184
inc count (9) Output (non-polled) 30918