TABLE C-3: Twelve C-Mores and One ACS/BMS II/BMS
Equip Point Name Name
Lon SNVT NAME Lon SNVT Lon Direction
5 01-Fire Rate Out boilerstate_5 AV:80
41 nvoBlrState5 inc count (9) Output (non-polled) 30009/5
5
effectsetpt_5 AV:81
42 nvoEffSetpt5 inc count (9) Output (non-polled) 30017/5
5
setpt_5
AV:82
43 nviSetpt5 inc count (9) Input (non-polling) 40001/5
5 05-Fire Rate In boilerload_5
AV:74
45 nvoBlrLoad5 inc count (9) Output (non-polled) 30018/5
5 06-Outlet Temp localsuptemp_5
AV:75
46 nvoLocSupTmp5 inc count (9) Output (non-polled) 30003/5
5 07-Display Code dispcode_5 AV:76
47 nvoDispCode5 inc count (9) Output (non-polled) 30001/5
5 08-Unit Status unitstat_5
AV:77
data
float
48 nvoUnitStat5 inc count (9) Output (non-polled)
5 09-Run Cycles runcycles_5 AV:78
49 nvoRunCycles5 51 Output (non-polled)
5 10-Run Hours runhours_5 AV:79
50 nvoRunHours5 51 Output (non-polled)
5 11-Oxygen o2level_5 AV:165
165 nvoO2Lev5 inc count (9) Output (non-polled) 30010/5
5 12-Exhaust Temp exhtemp_5
AV:185
185 nvoExhTmp5 inc count (9) Output (non-polled) 30007/5
Blr Addr 6
6 01-Fire Rate Out boilerstate_6 AV:90
51 nvoBlrState6 inc count (9) Output (non-polled) 30009/6
6
effectsetpt_6 AV:91
52 nvoEffSetpt6 inc count (9) Output (non-polled) 30017/6
6
setpt_6
AV:92
53 nviSetpt6 inc count (9) Input (non-polling) 40001/6
6 05-Fire Rate In boilerload_6
AV:84
55 nvoBlrLoad6 inc count (9) Output (non-polled) 30018/6