AERCO ProtoNode Gateway
User Manual
Page 78 of 126 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0080_0H
11/06/2014 Ph.: 800-526-0288 GF-129
TABLE C-3: Twelve C-Mores and One ACS/BMS II/BMS
Equip Point Name Name
Lon SNVT NAME Lon SNVT Lon Direction
6 06-Outlet Temp localsuptemp_6 AV:85
56 nvoLocSupTmp6 inc count (9) Output (non-polled) 30003/6
6 07-Display Code dispcode_6 AV:86
data
float
57 nvoDispCode6 inc count (9) Output (non-polled)
6 08-Unit Status unitstat_6 AV:87
58 nvoUnitStat6 inc count (9) Output (non-polled) 30002/6
6 09-Run Cycles runcycles_6 AV:88
59 nvoRunCycles6 51 Output (non-polled)
6 10-Run Hours runhours_6 AV:89
60 nvoRunHours6 51 Output (non-polled)
6 11-Oxygen o2level_6
AV:166
166 nvoO2Lev6 inc count (9) Output (non-polled) 30010/6
6 12-Exhaust Temp exhtemp_6
AV:186
186 nvoExhTmp6 inc count (9) Output (non-polled) 30007/6
Blr Addr 7
7 01-Fire Rate Out boilerstate_7
AV:100
61 nvoBlrState7 inc count (9) Output (non-polled) 30009/7
7
effectsetpt_7 AV:101
62 nvoEffSetpt7 inc count (9) Output (non-polled) 30017/7
7
setpt_7
AV:102
63 nviSetpt7 inc count (9) Input (non-polling) 40001/7
7 05-Fire Rate In boilerload_7
AV:94
65 nvoBlrLoad7 inc count (9) Output (non-polled) 30018/7
7 06-Outlet Temp localsuptemp_7 AV:95
66 nvoLocSupTmp7 inc count (9) Output (non-polled) 30003/7
7 07-Display Code dispcode_7 AV:96
67 nvoDispCode7 inc count (9) Output (non-polled) 30001/7
7 08-Unit Status unitstat_7 AV:97
68 nvoUnitStat7 inc count (9) Output (non-polled) 30002/7
7 09-Run Cycles runcycles_7
AV:98
69 nvoRunCycles7 51 Output (non-polled)
Comentarios a estos manuales